Área nominal de la sección transversal | Espesor de aislamiento | Espesor de la cinta de acero no magnética | Espesor de la cubierta | Diámetro externo aprox. | Peso aproximado | Resistencia máx. a corriente continua del conductor(20℃) | Capacidad portadora de corriente | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | Al aire (A) | A tierra (A) |
1X10 | 0.7 | 0.2 | 1.8 | 11.8 | 244.0 | 1.83 | 75 | 47 |
1X16 | 0.7 | 0.2 | 1.8 | 12.9 | 318.0 | 1.15 | 97 | 62 |
1X25 | 0.9 | 0.2 | 1.8 | 14.6 | 430.0 | 0.727 | 125 | 78 |
1X35 | 0.9 | 0.2 | 1.8 | 15.2 | 533.0 | 0.524 | 155 | 94 |
1X50 | 1.0 | 0.2 | 1.8 | 16.7 | 668.0 | 0.387 | 190 | 110 |
1X70 | 1.1 | 0.2 | 1.8 | 18.5 | 893.0 | 0.268 | 245 | 135 |
1X95 | 1.1 | 0.2 | 1.8 | 20.1 | 1157.0 | 0.193 | 300 | 160 |
1X120 | 1.2 | 0.2 | 1.8 | 21.7 | 1410.0 | 0.153 | 350 | 185 |
1X150 | 1.4 | 0.2 | 1.8 | 23.7 | 1705.0 | 0.124 | 400 | 205 |
1X185 | 1.6 | 0.2 | 1.8 | 25.7 | 2082.0 | 0.0991 | 460 | 235 |
1X240 | 1.7 | 0.2 | 1.8 | 28.0 | 2652.0 | 0.0754 | - | - |
1X300 | 1.8 | 0.2 | 1.9 | 31.0 | 3259.0 | 0.0601 | - | - |
1X400 | 2.0 | 0.2 | 2.0 | 35.0 | 4135.0 | 0.047 | - | - |