Área nominal de la sección transversal | Espesor de aislamiento | Espesor de la cinta de acero no magnética | Espesor de la cubierta | Diámetro externo aprox. | Peso aproximado | Resistencia máx. a corriente continua del conductor(20℃) | Capacidad portadora de corriente | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | Al aire (A) | A tierra (A) |
3X4+1X2.5 | 0.7/0.7 | 0.2 | 1.8 | 15.5 | 368 | 4.61/7.41 | - | 50 |
3X6+1X4 | 0.7/0.7 | 0.2 | 1.8 | 16.8 | 465 | 3.08/4.61 | - | 60 |
3X10+1X6 | 0.7/0.7 | 0.2 | 1.8 | 19.3 | 633 | 1.83/3.08 | 64 | 85 |
3X16+1X10 | 0.7/0.7 | 0.2 | 1.8 | 22.1 | 890 | 1.15/1.83 | 83 | 110 |
3X25+1X16 | 0.9/0.7 | 0.2 | 1.8 | 25.1 | 1272 | 0.727/1.15 | 110 | 140 |
3X35+1X16 | 0.9/0.7 | 0.2 | 1.8 | 26.8 | 1583 | 0.524/1.15 | 135 | 170 |
3X50+1X25 | 1/0.9 | 0.2 | 1.9 | 30.2 | 2030 | 0.387/0.727 | 165 | 200 |
3X70+1X35 | 1.1/0.9 | 0.2 | 2.0 | 35.1 | 2810 | 0.268/0.524 | 210 | 245 |
3X95+1X50 | 1.1/1.0 | 0.5 | 2.2 | 40.4 | 4135 | 0.193/0.387 | 260 | 300 |
3X120+1X70 | 1.2/1.1 | 0.5 | 2.3 | 45 | 5135 | 0.153/0.268 | 305 | 335 |
3X150+1X70 | 1.4/1.1 | 0.5 | 2.5 | 49.1 | 6120 | 0.124/0.268 | 345 | 380 |
3X185+1X95 | 1.6/1.1 | 0.5 | 2.8 | 54.3 | 7616 | 0.0991/0.193 | 395 | 430 |
3X240+1X120 | 1.7/1.2 | 0.5 | 2.8 | 59.1 | 9679 | 0.0754/0.153 | 465 | 500 |
3X300+1X150 | 1.8/1.4 | 0.5 | 3.0 | 66 | 11889 | 0.0601/0.124 | 535 | 565 |