Área nominal de la sección transversal | Espesor de aislamiento | Espesor de la cinta de acero no magnética | Espesor de la cubierta | Diámetro externo aprox. | Peso aproximado | Resistencia máx. a corriente continua del conductor(20℃) | Capacidad portadora de corriente | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | Al aire (A) | A tierra (A) |
3*4+2*2.5 | 1.0/0.8 | 0.2 | 1.8 | 17.5 | 410 | 7.41/12.1 | - | - |
3*6+2*4 | 1.0/1.0 | 0.2 | 1.8 | 19.3 | 495 | 4.61/7.41 | - | - |
3*10+2*6 | 1.0/1.0 | 0.2 | 1.8 | 21.8 | 621 | 3.08/4.61 | 38 | 54 |
3*16+2*10 | 1.0/1.0 | 0.2 | 1.8 | 25.0 | 797 | 1.91/3.08 | 51 | 71 |
3*25+2*16 | 1.2/1.0 | 0.2 | 1.9 | 28.9 | 1058 | 1.2/1.91 | 66 | 92 |
3*35+2*16 | 1.2/1.0 | 0.2 | 1.9 | 30.0 | 1178 | 0.868/1.91 | 81 | 110 |
3*50+2*25 | 1.4/1.2 | 0.2 | 2.1 | 35.6 | 1603 | 0.641/1.2 | 98 | 130 |
3*70+2*35 | 1.4/1.2 | 0.5 | 2.3 | 40.2 | 2365 | 0.443/0.868 | 120 | 160 |
3*95+2*50 | 1.6/1.4 | 0.5 | 2.4 | 45.8 | 3015 | 0.32/0.641 | 150 | 195 |
3*120+2*70 | 1.6/1.4 | 0.5 | 2.6 | 50.5 | 3645 | 0.253/0.443 | 180 | 225 |
3*150+2*70 | 1.8/1.4 | 0.5 | 2.7 | 53.8 | 4110 | 0.206/0.443 | 205 | 250 |
3*185+2*95 | 2.0/1.6 | 0.5 | 2.9 | 60.2 | 5090 | 0.164/0.32 | 235 | 285 |
3*240+2*120 | 2.2/1.6 | 0.5 | 3.1 | 66.4 | 6195 | 0.125/0.253 | 280 | 330 |
3*300+2*150 | 2.4/1.8 | 0.5 | 3.3 | 73.0 | 7421 | 0.1/0.206 | 320 | 370 |